2.1.3.3
Settings
Addr.
Parameter
201
CT Starpoint
202
Vnom PRIMARY
203
Vnom SECONDARY
204
CT PRIMARY
205
CT SECONDARY
206A
Vph / Vdelta
209
PHASE SEQ.
210A
TMin TRIP CMD
211A
TMax CLOSE CMD
212
BkrClosed I MIN
213
VT Connect. 3ph
214
Rated Frequency
215
Distance Unit
217
Ignd-CT PRIM
218
Ignd-CT SEC
235A
ATEX100
240
VT Connect. 1ph
250A
50/51 2-ph prot
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Addresses which have an appended "A" can only be changed with DIGSI, under "Dis-
play Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates
the corresponding secondary nominal current of the current transformer.
C
Setting Options
towards Line
towards Busbar
0.10 .. 800.00 kV
100 .. 225 V
10 .. 50000 A
1A
5A
1.00 .. 3.00
A B C
A C B
0.01 .. 32.00 sec
0.01 .. 32.00 sec
1A
0.04 .. 1.00 A
5A
0.20 .. 5.00 A
Van, Vbn, Vcn
Vab, Vbc, VGnd
Van,Vbn,Vcn,VGn
Van,Vbn,Vcn,VSy
50 Hz
60 Hz
km
Miles
1 .. 50000 A
1A
5A
NO
YES
NO
Van
Vbn
Vcn
Vab
Vbc
Vca
ON
OFF
Default Setting
towards Line
CT Starpoint
12.00 kV
Rated Primary Voltage
100 V
Rated Secondary Voltage
(L-L)
100 A
CT Rated Primary Current
1A
CT Rated Secondary
Current
1.73
Matching ratio Phase-VT
To Open-Delta-VT
A B C
Phase Sequence
0.15 sec
Minimum TRIP Command
Duration
1.00 sec
Maximum Close
Command Duration
0.04 A
Closed Breaker Min.
Current Threshold
0.20 A
Van, Vbn, Vcn
VT Connection, three-
phase
50 Hz
Rated Frequency
km
Distance measurement
unit
60 A
Ignd-CT rated primary
current
1A
Ignd-CT rated secondary
current
NO
Storage of th. Replicas w/o
Power Supply
NO
VT Connection, single-
phase
OFF
50, 51 Time Overcurrent
with 2ph. prot.
2.1 General
Comments
48