2.11.3 Malfunction Responses of the Monitoring Functions
2.11.3.1 Description
Malfunction Re-
sponses
Monitoring
AC/DC supply voltage
loss
Internal supply voltages Internal (power supply)
Battery
Hardware Watchdog
Software watchdog
Working memory ROM Internal (hardware)
Program memory RAM Internal (hardware)
Settings
Sampling frequency
Error in the I/O-board
Module error
Internal auxiliary
voltage 5 V
0-V Monitoring
Internal auxiliary
voltage –5 V
Offset monitoring
Internal supply voltages Internal (hardware)
Current Sum
Current symmetry
Voltage symmetry
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
In the following malfunction responses of monitoring equipment are clearly listed.
Depending on the type of malfunction discovered, an annunciation is sent, a restart of
the processor system is initiated, or the device is taken out of service. After three un-
successful restart attempts, the device is taken out of service. The live status contact
operates to indicate the device is malfunctioning. In addition, if the internal auxiliary
supply is present, the red LED "ERROR" lights up on the front cover and the green
"RUN" LED goes out. If the internal power supply fails, then all LEDs are dark. Table
2-11 shows a summary of the monitoring functions and the malfunction responses of
the relay.
Table 2-11
Summary of Malfunction Responses by the Protection Relay
Possible Causes
External (aux. voltage) inter-
nal (power supply)
Internal (battery)
Internal (processor failure)
Internal (processor failure)
Internal (hardware)
Internal (hardware)
Internal (hardware)
Internal (hardware)
Internal (hardware)
Internal (hardware)
Internal (hardware)
Internal (hardware)
Internal (measured value ac-
quisition)
External (power system or
current transformer)
External (power system or
voltage transformer)
Malfunction
Response
Device shutdown
All LEDs dark
Device shutdown
LED "ERROR"
Annunciation
„Fail Battery" (177)
1)
Device shutdown
LED "ERROR"
1)
Restart attempt
LED "ERROR"
Relay aborts restart,
LED blinks
Device shutdown
During boot sequence
LED "ERROR"
During operation:
LED "ERROR"
1)
Restart attempt
1)
Restart attempt
LED "ERROR"
Device shutdown
LED "ERROR"
Device shutdown
„I/O-Board error" (178),
LED "ERROR"
Device shutdown
„Error Board 1" to „Error
Board 7" (178 to 189),
LED "ERROR"
Device shutdown
„Error 5V" (144),
LED "ERROR"
Device shutdown
„Error 0V" (145),
LED "ERROR"
Device shutdown
„Error -5V" (146),
LED "ERROR"
Device shutdown
„Error Offset" (191)
Device shutdown
„Error PwrSupply" (147),
LED "ERROR"
„Failure Σ I" (162)
Annunciation
Annunciation
„Fail I balance" (163)
Annunciation
„Fail V balance" (167)
2.11 Monitoring Functions
Message (No.)
DOK
DOK
DOK
DOK
DOK
DOK
DOK
DOK
DOK
DOK
DOK
DOK
DOK
DOK
DOK
As allocated
As allocated
As allocated
Output
2)
drops out
2)
drops out
2)
drops out
2)
drops out
2)
drops out
2)
drops out
2)
drops out
2)
drops out
2)
drops out
2)
drops out
2)
drops out
2)
drops out
2)
drops out
2)
drops out
2)
drops out
198