Siemens siprotec SJ62 User Manual page 657

Multi-functional protective relay with local control
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
6321
Balancing V1/V2
6322A
ANGLE ADJUSTM.
6323
CONNECTIONof V2
6325
VT Vn2, primary
6330
dV ASYN V2>V1
6331
dV ASYN V2<V1
6332
df ASYN f2>f1
6333
df ASYN f2<f1
6340
SYNC PERMIS.
6341
F SYNCHRON
6342
dV SYNC V2>V1
6343
dV SYNC V2<V1
dα SYNC α2> α1
6344
dα SYNC α2< α1
6345
6346
T SYNC-DELAY
6350
dV SYNCHK V2>V1
6351
dV SYNCHK V2<V1
6352
df SYNCHK f2>f1
6353
df SYNCHK f2<f1
dα SYNCHK α2>α1
6354
dα SYNCHK α2<α1
6355
6401
Synchronizing
6402
SyncCB
6403
Vmin
6404
Vmax
6405
V<
6406
V>
6407
SYNC V1<V2>
6408
SYNC V1>V2<
6409
SYNC V1<V2<
6410A
Direct CO
6411A
TSUP VOLTAGE
6412
T-SYN. DURATION
6413A
25 Synchron
655
Function
C
SYNC function 3
0.50 .. 2.00
0 .. 360 °
SYNC function 3
SYNC function 3
A-G
B-G
C-G
A-B
B-C
C-A
SYNC function 3
0.10 .. 800.00 kV
SYNC function 3
0.5 .. 50.0 V
SYNC function 3
0.5 .. 50.0 V
SYNC function 3
0.01 .. 2.00 Hz
SYNC function 3
0.01 .. 2.00 Hz
SYNC function 3
YES
NO
SYNC function 3
0.01 .. 0.04 Hz
SYNC function 3
0.5 .. 50.0 V
SYNC function 3
0.5 .. 50.0 V
2 .. 80 °
SYNC function 3
2 .. 80 °
SYNC function 3
SYNC function 3
0.00 .. 60.00 sec
SYNC function 3
0.5 .. 50.0 V
SYNC function 3
0.5 .. 50.0 V
SYNC function 3
0.01 .. 2.00 Hz
SYNC function 3
0.01 .. 2.00 Hz
2 .. 80 °
SYNC function 3
2 .. 80 °
SYNC function 3
SYNC function 4
ON
OFF
SYNC function 4
(Setting options depend
on configuration)
SYNC function 4
20 .. 125 V
SYNC function 4
20 .. 140 V
SYNC function 4
1 .. 60 V
SYNC function 4
20 .. 140 V
SYNC function 4
YES
NO
SYNC function 4
YES
NO
SYNC function 4
YES
NO
SYNC function 4
YES
NO
SYNC function 4
0.00 .. 60.00 sec
0.01 .. 1200.00 sec; ∞
SYNC function 4
SYNC function 4
YES
NO
Setting Options
Default Setting
1.00
0 °
A-B
12.00 kV
2.0 V
2.0 V
0.10 Hz
0.10 Hz
YES
0.01 Hz
5.0 V
5.0 V
10 °
10 °
0.00 sec
5.0 V
5.0 V
0.10 Hz
0.10 Hz
10 °
10 °
OFF
None
90 V
110 V
5 V
80 V
NO
NO
NO
NO
0.10 sec
30.00 sec
YES
Comments
Balancing factor V1/V2
Angle adjustment (transformer)
Connection of V2
VT nominal voltage V2, primary
Maximum voltage difference
V2>V1
Maximum voltage difference
V2<V1
Maximum frequency difference
f2>f1
Maximum frequency difference
f2<f1
Switching at synchronous condi-
tions
Frequency threshold ASYN <-->
SYN
Maximum voltage difference
V2>V1
Maximum voltage difference
V2<V1
Maximum angle difference
alpha2>alpha1
Maximum angle difference
alpha2<alpha1
Release delay at synchronous
conditions
Maximum voltage difference
V2>V1
Maximum voltage difference
V2<V1
Maximum frequency difference
f2>f1
Maximum frequency difference
f2<f1
Maximum angle difference
alpha2>alpha1
Maximum angle difference
alpha2<alpha1
Synchronizing Function
Synchronizable circuit breaker
Minimum voltage limit: Vmin
Maximum voltage limit: Vmax
Threshold V1, V2 without voltage
Threshold V1, V2 with voltage
ON-Command at V1< and V2>
ON-Command at V1> and V2<
ON-Command at V1< and V2<
Direct ON-Command
Supervision time of V1>;V2> or
V1<;V2<
Maximum duration of Synchroni-
zation
Switching at synchronous condi-
tion
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec sj63Siprotec sj64

Table of Contents