Settings - Siemens siprotec SJ62 User Manual

Multi-functional protective relay with local control
Table of Contents

Advertisement

2 Functions
Note Regarding
Settings List for Au-
tomatic Reclosure
Function

2.14.7 Settings

Addr.
Parameter
7101
FCT 79
7103
BLOCK MC Dur.
7105
TIME RESTRAINT
7108
SAFETY 79 ready
7113
CHECK CB?
7114
T-Start MONITOR
7115
CB TIME OUT
7116
Max. DEAD EXT.
7117
T-ACTION
7118
T DEAD DELAY
7127
DEADTIME 1: PH
7128
DEADTIME 1: G
7129
DEADTIME 2: PH
7130
DEADTIME 2: G
7131
DEADTIME 3: PH
7132
DEADTIME 3: G
7133
DEADTIME 4: PH
7134
DEADTIME 4: G
7135
# OF RECL. GND
7136
# OF RECL. PH
7137
Cmd.via control
7138
Internal SYNC
7139
External SYNC
7140
ZONE SEQ.COORD.
247
The setting options of address 7137 Cmd.via control are generated dynamically
according to the current configuration.
Address 7138 Internal SYNC is only available for 7SJ64.
Setting Options
OFF
ON
0.50 .. 320.00 sec; 0
0.50 .. 320.00 sec
0.01 .. 320.00 sec
No check
Chk each cycle
0.01 .. 320.00 sec; ∞
0.10 .. 320.00 sec
0.50 .. 1800.00 sec; ∞
0.01 .. 320.00 sec; ∞
0.0 .. 1800.0 sec; ∞
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0 .. 9
0 .. 9
(Setting options depend
on configuration)
(Setting options depend
on configuration)
YES
NO
OFF
ON
Default Setting
OFF
79 Auto-Reclose Function
1.00 sec
AR blocking duration after manual
close
3.00 sec
79 Auto Reclosing reset time
0.50 sec
Safety Time until 79 is ready
No check
Check circuit breaker before AR?
0.50 sec
AR start-signal monitoring time
3.00 sec
Circuit Breaker (CB) Supervision
Time
100.00 sec
Maximum dead time extension
∞ sec
Action time
1.0 sec
Maximum Time Delay of Dead-
Time Start
0.50 sec
Dead Time 1: Phase Fault
0.50 sec
Dead Time 1: Ground Fault
0.50 sec
Dead Time 2: Phase Fault
0.50 sec
Dead Time 2: Ground Fault
0.50 sec
Dead Time 3: Phase Fault
0.50 sec
Dead Time 3: Ground Fault
0.50 sec
Dead Time 4: Phase Fault
0.50 sec
Dead Time 4: Ground Fault
1
Number of Reclosing Cycles
Ground
1
Number of Reclosing Cycles
Phase
None
Close command via control
device
None
Internal 25 synchronisation
NO
External 25 synchronisation
OFF
ZSC - Zone sequence coordina-
tion
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015