Siemens siprotec SJ62 User Manual page 400

Multi-functional protective relay with local control
Table of Contents

Advertisement

Pickup Voltages of
BI8 to BI20 for
7SJ642*-
Pickup Voltages of
BI8 to BI33 for
7SJ645*-
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Table 3-26
Jumper settings for the pickup voltages of the binary inputs BI8 to BI20 on the
B–I/O-2 board for model 7SJ642*-... (housing size
Binary Inputs
Slot 19
BI8
BI9
BI10
BI 11
BI12
BI13
BI14
BI15
BI16
BI17
BI18
BI19
BI20
1)
Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 to 220 VDC and 115 VAC or
115 to 230 VAC
Table 3-27
Jumper settings for the pickup voltages of the binary inputs BI8 to BI33 on the
B–I/O-2 board for model 7SJ645*-... (housing size
Binary Inputs
Slot 33 left
Slot 19 right
side
side
BI8
BI21
BI9
BI22
BI10
BI23
BI11
BI24
BI12
BI25
BI13
BI26
BI14
BI27
BI15
BI28
BI16
BI29
BI17
BI30
BI18
BI31
BI19
BI32
BI20
BI33
1)
Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 to 220 VDC and 115 VAC or
115 to 230 VAC
Jumpers X71, X72 and X73 on the input/output module B-I/O-2 serve to set up the
Bus Address. The jumpers must not be changed. The following two tables list the
jumper presettings.
Jumper
19 VDC Pickup
X21
X22
X23
X24
X25
X26
X27
X28
X29
X30
X31
X32
X33
Jumper
19 VDC Pickup
X21
1-2
X22
1-2
X23
1-2
X24
1-2
X25
1-2
X26
1-2
X27
1-2
X28
1-2
X29
1-2
X30
1-2
X31
1-2
X32
1-2
X33
1-2
3.1 Mounting and Connections
1
/
)
2
1)
88 VDC Pickup
1-2
2-3
1-2
2-3
1-2
2-3
1-2
2-3
1-2
2-3
1-2
2-3
1-2
2-3
1-2
2-3
1-2
2-3
1-2
2-3
1-2
2-3
1-2
2-3
1-2
2-3
1
/
)
1
1)
88 VDC Pickup
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2)
2)
398

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec sj63Siprotec sj64