3 Mounting and Commissioning
Pickup Voltages of
BI8 to BI15 for
7SJ641*-
Contact Mode
PCB Addresses
401
Table 3-30
Jumper settings for the pickup voltages of the binary inputs BI8 to BI15 on the
C–I/O-1 board for model 7SJ641*-
Binary Inputs
Jumper
BI8
X21/X22
BI9
X23/X24
BI10
X25/X26
BI11
X27/X28
BI12
X29/X30
BI13
X31/X32
BI14
X33/X34
BI15
X35/X36
1)
Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 to 220 VDC and 115 VAC or
115 to 230 VAC
3)
Use only with pickup voltages 220 or 250 VDC
With models 7SJ641 binary output BO6 can be changed from normally open to nor-
mally closed operation. The following table shows the setting of jumper X40 regarding
the contact mode.
Table 3-31
Jumper settings for contact mode of the binary output BO6 on the C–I/O-1
board
Jumper
Open in quiescent state
(NO)
X40
Jumpers X71, X72 and X73 on the input/output board C-I/O-1 are used to set the bus
address and must not be changed. The following table lists the jumper presettings.
The slots of the boards are shown in Figure 3-7.
Table 3-32
Jumper Settings of Module Addresses of C–I/O-1 board for 7SJ64
Jumper
Presetting
X71
X72
X73
19 VDC Pickup
1)
L
L
L
L
L
L
L
L
Closed in quiescent state
1-2
H
L
H
88 VDC Pickup
176 VDC Pickup
2)
M
M
M
M
M
M
M
M
Presetting
(NC)
2-3
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
3)
H
H
H
H
H
H
H
H
1-2