2 Functions
Addr.
Parameter
260
Ir-52
261
OP.CYCLES AT Ir
262
Isc-52
263
OP.CYCLES Isc
264
Ix EXPONENT
265
Cmd.via control
266
T 52 BREAKTIME
267
T 52 OPENING
276
TEMP. UNIT
613A
Gnd O/Cprot. w.
614A
OP. QUANTITY 59
615A
OP. QUANTITY 27
2.1.3.4

Information List

No.
Information
5145
>Reverse Rot.
5147
Rotation ABC
5148
Rotation ACB
49
C
Setting Options
10 .. 50000 A
100 .. 1000000
10 .. 100000 A
1 .. 1000
1.0 .. 3.0
(Setting options depend
on configuration)
1 .. 600 ms
1 .. 500 ms
Celsius
Fahrenheit
Ignd (measured)
3I0 (calcul.)
Vphph
V2
V1
Vphph
Type of In-
formation
SP
>Reverse Phase Rotation
OUT
Phase rotation ABC
OUT
Phase rotation ACB
Default Setting
125 A
Rated Normal Current (52
Breaker)
10000
Switching Cycles at Rated
Normal Current
25000 A
Rated Short-Circuit Break-
ing Current
50
Switch. Cycles at Rated
Short-Cir. Curr.
2.0
Exponent for the Ix-
Method
None
52 B.Wear: Open Cmd. via
Control Device
80 ms
Breaktime (52 Breaker)
65 ms
Opening Time (52 Break-
er)
Celsius
Unit of temperature mea-
surement
Ignd (measured)
Ground Overcurrent pro-
tection with
Vphph
Opera. Quantity for 59 Ov-
ervolt. Prot.
V1
Opera. Quantity for 27 Un-
dervolt. Prot.
Comments
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015