Siemens siprotec SJ62 User Manual page 383

Multi-functional protective relay with local control
Table of Contents

Advertisement

3 Mounting and Commissioning
Power Supply
Pickup Voltages of
BI1 to BI3
Contact Mode for
Binary Outputs
BO1 and BO2
381
Table 3-4
Jumper settings for the nominal voltage of the integrated power supply on the
processor board A–CPU for 7SJ62.../EE
Jumper
24/48 VDC
X51
Not used
X52
Not used
X53
Not used
cannot be changed
Table 3-5
Jumper settings for the pickup voltages of the binary inputs BI1 to BI3 on the
processor printed circuit board A–CPU for 7SJ62.../EE
Binary Inputs
BI1
BI2
BI3
1)
Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 VDC to 220 VDC and 115/230
VAC
Table 3-6
Jumper settings for the contact mode of the binary inputs BI1 to BI3 on the pro-
cessor printed circuit board A–CPU for 7SJ62.../EE
for
Jumper
Open in quiescent
BO1
X41
BO2
X42
Nominal Voltage
60 to 125 VDC
1-2
1-2 and 3-4
1-2
Jumper
19 VDC Pickup
X21
X22
X23
Closed in quiescent
state (NO)
1-2
1-2
110 to 250 VDC
115 to 230 VAC
2-3
2-3
2-3
interchangeable
1)
88 VDC Pickup
L
L
L
Presetting
state (NC)
2-3
2-3
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
2)
H
H
H
1-2
1-2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec sj63Siprotec sj64

Table of Contents