Siemens siprotec SJ62 User Manual page 654

Multi-functional protective relay with local control
Table of Contents

Advertisement

Addr.
Parameter
5102
27-1 PICKUP
5103
27-1 PICKUP
5106
27-1 DELAY
5110
27-2 PICKUP
5111
27-2 PICKUP
5112
27-2 DELAY
5113A
27-1 DOUT RATIO
5114A
27-2 DOUT RATIO
5120A
CURRENT SUPERV.
5301
FUSE FAIL MON.
5302
FUSE FAIL 3Vo
5303
FUSE FAIL RESID
5401
FCT 81 O/U
5402
Vmin
5403
81-1 PICKUP
5404
81-1 PICKUP
5405
81-1 DELAY
5406
81-2 PICKUP
5407
81-2 PICKUP
5408
81-2 DELAY
5409
81-3 PICKUP
5410
81-3 PICKUP
5411
81-3 DELAY
5412
81-4 PICKUP
5413
81-4 PICKUP
5414
81-4 DELAY
6101
Synchronizing
6102
SyncCB
6103
Vmin
6104
Vmax
6105
V<
6106
V>
6107
SYNC V1<V2>
6108
SYNC V1>V2<
6109
SYNC V1<V2<
6110A
Direct CO
6111A
TSUP VOLTAGE
6112
T-SYN. DURATION
6113A
25 Synchron
6120
T-CB close
6121
Balancing V1/V2
6122A
ANGLE ADJUSTM.
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Function
C
27/59 O/U Volt.
10 .. 210 V
27/59 O/U Volt.
10 .. 120 V
0.00 .. 100.00 sec; ∞
27/59 O/U Volt.
27/59 O/U Volt.
10 .. 210 V
27/59 O/U Volt.
10 .. 120 V
0.00 .. 100.00 sec; ∞
27/59 O/U Volt.
27/59 O/U Volt.
1.01 .. 3.00
27/59 O/U Volt.
1.01 .. 3.00
27/59 O/U Volt.
OFF
ON
Measurem.Superv
ON
OFF
Measurem.Superv
10 .. 100 V
Measurem.Superv
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
81 O/U Freq.
OFF
ON
81 O/U Freq.
10 .. 150 V
81 O/U Freq.
45.50 .. 54.50 Hz
81 O/U Freq.
55.50 .. 64.50 Hz
0.00 .. 100.00 sec; ∞
81 O/U Freq.
81 O/U Freq.
45.50 .. 54.50 Hz
81 O/U Freq.
55.50 .. 64.50 Hz
0.00 .. 100.00 sec; ∞
81 O/U Freq.
81 O/U Freq.
45.50 .. 54.50 Hz
81 O/U Freq.
55.50 .. 64.50 Hz
0.00 .. 100.00 sec; ∞
81 O/U Freq.
81 O/U Freq.
45.50 .. 54.50 Hz
81 O/U Freq.
55.50 .. 64.50 Hz
0.00 .. 100.00 sec; ∞
81 O/U Freq.
SYNC function 1
ON
OFF
SYNC function 1
(Setting options depend
on configuration)
SYNC function 1
20 .. 125 V
SYNC function 1
20 .. 140 V
SYNC function 1
1 .. 60 V
SYNC function 1
20 .. 140 V
SYNC function 1
YES
NO
SYNC function 1
YES
NO
SYNC function 1
YES
NO
SYNC function 1
YES
NO
SYNC function 1
0.00 .. 60.00 sec
0.01 .. 1200.00 sec; ∞
SYNC function 1
SYNC function 1
YES
NO
SYNC function 1
0.01 .. 0.60 sec
SYNC function 1
0.50 .. 2.00
0 .. 360 °
SYNC function 1
Setting Options
Default Setting
75 V
75 V
1.50 sec
70 V
70 V
0.50 sec
1.20
1.20
ON
OFF
30 V
0.10 A
0.50 A
OFF
65 V
49.50 Hz
59.50 Hz
60.00 sec
49.00 Hz
59.00 Hz
30.00 sec
47.50 Hz
57.50 Hz
3.00 sec
51.00 Hz
61.00 Hz
30.00 sec
OFF
None
90 V
110 V
5 V
80 V
NO
NO
NO
NO
0.10 sec
30.00 sec
YES
0.06 sec
1.00
0 °
A.8 Settings
Comments
27-1 Pickup
27-1 Pickup
27-1 Time Delay
27-2 Pickup
27-2 Pickup
27-2 Time Delay
27-1 Dropout Ratio
27-2 Dropout Ratio
Current Supervision
Fuse Fail Monitor
Zero Sequence Voltage
Residual Current
81 Over/Under Frequency Pro-
tection
Minimum required voltage for op-
eration
81-1 Pickup
81-1 Pickup
81-1 Time Delay
81-2 Pickup
81-2 Pickup
81-2 Time Delay
81-3 Pickup
81-3 Pickup
81-3 Time delay
81-4 Pickup
81-4 Pickup
81-4 Time delay
Synchronizing Function
Synchronizable circuit breaker
Minimum voltage limit: Vmin
Maximum voltage limit: Vmax
Threshold V1, V2 without voltage
Threshold V1, V2 with voltage
ON-Command at V1< and V2>
ON-Command at V1> and V2<
ON-Command at V1< and V2<
Direct ON-Command
Supervision time of V1>;V2> or
V1<;V2<
Maximum duration of Synchroni-
zation
Switching at synchronous condi-
tion
Closing (operating) time of CB
Balancing factor V1/V2
Angle adjustment (transformer)
652