Siemens siprotec SJ62 User Manual page 389

Multi-functional protective relay with local control
Table of Contents

Advertisement

3 Mounting and Commissioning
Power Supply
Live Status Contact
Pickup Voltages of
BI1 to BI7
387
Table 3-11
Jumper settings for the nominal voltage of the integrated power supply on the
processor board B–CPU for 7SJ63.../EE
Jumper
60/110/125 VDC
X51
X52
1-2 and 3-4
X53
Table 3-12
Jumper setting for the quiescent state of the live status contact on the proces-
sor printed circuit board B-CPU for devices 7SJ63.../EE
Jumper
Open in the quiescent
X40
Table 3-13
Jumper settings for pickup voltages of binary inputs BI1 to BI7 on the proces-
sor printed circuit board B–CPU for 7SJ63.../EE
Binary Inputs
BI1
BI2
BI3
BI4
BI5
BI6
BI7
1)
Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 220/250 VDC and 115/230 VAC
Nominal Voltage
220/250 VDC
115/230 VAC
1-2
1-2
interchangeable
Closed in the quiescent
state
1-2
Jumper
19 VDC Pickup
X21
X22
X23
X24
X25
X26
X27
24/48 VDC
2-3
2-3
2-3
cannot be changed
Factory Setting
state
2-3
1)
88 VDC Pickup
L
L
L
L
L
L
L
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
1-2
none
none
2-3
2)
H
H
H
H
H
H
H

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec sj63Siprotec sj64

Table of Contents