Siemens siprotec SJ62 User Manual page 85

Multi-functional protective relay with local control
Table of Contents

Advertisement

2 Functions
Addr.
Parameter
1204
50-1 PICKUP
1205
50-1 DELAY
1207
51 PICKUP
1208
51 TIME DIAL
1209
51 TIME DIAL
1210
51 Drop-out
1211
51 IEC CURVE
1212
51 ANSI CURVE
1213A
MANUAL CLOSE
1214A
50-2 active
1215A
50 T DROP-OUT
1230
51/51N
1231
MofPU Res T/Tp
1301
FCT 50N/51N
1302
50N-2 PICKUP
1303
50N-2 DELAY
1304
50N-1 PICKUP
1305
50N-1 DELAY
1307
51N PICKUP
1308
51N TIME DIAL
1309
51N TIME DIAL
83
C
Setting Options
0.10 .. 35.00 A; ∞
1A
0.50 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.50 .. 15.00 ; ∞
Instantaneous
Disk Emulation
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
50-2 instant.
50 -1 instant.
51 instant.
Inactive
Always
with 79 active
0.00 .. 60.00 sec
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
ON
OFF
0.05 .. 35.00 A; ∞
1A
0.25 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
0.05 .. 35.00 A; ∞
1A
0.25 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.50 .. 15.00 ; ∞
Default Setting
1.00 A
50-1 Pickup
5.00 A
0.50 sec
50-1 Time Delay
1.00 A
51 Pickup
5.00 A
0.50 sec
51 Time Dial
5.00
51 Time Dial
Disk Emulation
Drop-out characteristic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
50-2 instant.
Manual Close Mode
Always
50-2 active
0.00 sec
50 Drop-Out Time Delay
51/51N
Multiple of Pickup <-> T/Tp
ON
50N, 51N Ground Time
Overcurrent
0.50 A
50N-2 Pickup
2.50 A
0.10 sec
50N-2 Time Delay
0.20 A
50N-1 Pickup
1.00 A
0.50 sec
50N-1 Time Delay
0.20 A
51N Pickup
1.00 A
0.20 sec
51N Time Dial
5.00
51N Time Dial
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Comments