Warning Alarm Levels; Temperature Rise Calculation Method - Siemens 7UT51 Instruction Manual

Protective relay
Hide thumbs Also See for 7UT51:
Table of Contents

Advertisement

7UT51 v3
Example: If the short-time overload capacity is stated
for a duration of 1 s, then that short-term
current is inserted into the above formula.
1
permissible 1s current
τ
×
----- -
=
----------------------------------------------------------------------------- -
60
continuously permissible current
Note: The result becomes more inaccurate the
longer the stated duration of the current
becomes.
2403 49 Tconst 1
2503 49 Tconst 2
Thermal overload time constant τ
Range: 1.0
Default: 100.0 minutes
The single-body thermal body model used by the relay
is appropriate for small continuous overloads (up to
approximately 1.2 times the rated current). For larger
continuous overloads, it is sufficient to set a slightly
shorter time constant which considers the faster
warm-up of the winding as compared to the iron.
9.3.3

Warning Alarm Levels

The element can generate a warning-alarm event prior
to the pickup event. The alarm event can be
configured to trip and output contacts to take
corrective actions (load shedding, activation of cooling
equipment, etc.).
Two types of warning exist; one based on temperature
rise, and the other based directly on the overload
current.
The warning based on temperature rise occurs when
the calculated temperature rise reaches a specified
percentage of the trip value. Of course, the warning
level should be less than 100% of the trip-level
temperature rise (Q
), and higher than the
trip
temperature at the allowed maximum continuous
overload current (Q
), which can be calculated from
cont
the k factor:
Θ
Θ
1
cont
<
---- -
-------------
-------------- -
=
Θ
Θ
2
k
trip
PRIM-2330C
2
999.9 minutes
Θ
warn
trip
<
----------- -
=
100%
Θ
trip
trip
Thermal Overload Protection (49-1, 49-2)
For example, if k is 1.1, then 1/k
should be more than 83% (the allowed continuous
overload current) and less than 100% (the trip-level
temperature rise).
2404 49Θ Θ Θ Θ ALRM1
2504 49Θ Θ Θ Θ ALRM2
Temperature rise that will cause a warning
alarm (specified as a percentage of the
temperature rise that will cause a pickup).
Range: 50
Default: 90%
The warning based on the overload current occurs
when the measured current reaches a specified
multiple of the rated current:
2405 ALRM1
2505 ALRM2
Warning
specified as a multiple or fraction of I
Range: 0.10
Default: 1.10 I
9.3.4
Temperature Rise
Calculation Method
The calculated temperature rise may be different for
each phase of the protected winding. Address 2406
(or 2506) specifies whether to use as the value of Q
the maximum of the three temperature values (one for
each phase current), the mean temperature value, or
the temperature rise calculated based on the largest
phase current.
2406 TEMP METH1
2506 TEMP METH2
Method for calculation of instantaneous temperature Θ.
Option
Θ max
Average Θ
Θ at Imax
(9.5)
2
is 83%, so Q
100% of pickup temperature rise
-
level continuous thermal current,
4.00 I/I
n
n
Description
Calculate the temperature for each
phase current, then use the maximum
(default).
Calculate the temperature for each
phase current, then use the average.
Identify the largest phase current,
then calculate and use its
temperature.
9
warn
.
N
109