Siemens siprotec SJ62 User Manual page 93

Multi-functional protective relay with local control
Table of Contents

Advertisement

2 Functions
Figure 2-19
Logic diagram of the directional high-current element 67-2 for phases
91
The following figure shows by way of example the logic diagram for the high-set
element 67-2.
If parameter MANUAL CLOSE is set to 67-2 instant. and manual close detection
applies, the pickup is tripped instantaneously, also if the element is blocked via binary
input. The same applies to 79 AR 67-2 instantaneous.
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015