2.6.5

Settings

Addr.
Parameter
5001
FCT 59
5002
59-1 PICKUP
5003
59-1 PICKUP
5004
59-1 DELAY
5005
59-2 PICKUP
5006
59-2 PICKUP
5007
59-2 DELAY
5015
59-1 PICKUP V2
5016
59-2 PICKUP V2
5017A
59-1 DOUT RATIO
5018A
59-2 DOUT RATIO
5101
FCT 27
5102
27-1 PICKUP
5103
27-1 PICKUP
5106
27-1 DELAY
5110
27-2 PICKUP
5111
27-2 PICKUP
5112
27-2 DELAY
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
this feature prevents an immediate general pickup of the device when the device is
powered-up without measurement voltage being present.
Note
If parameter CURRENT SUPERV. is set to disabled in address 5120, the device picks
up without measurement voltage and the undervoltage protection function in pickup.
Further configuration can be performed by pickup of measurement voltage or blocking
voltage protection. The latter can be initiated via device operation in DIGSI and via
communication from the control centre by means of a tagging command for blocking
voltage protection. This causes the dropout of the pickup and parameterization can be
resumed.
Please note that pickup threshold BkrClosed I MIN is used in other protective func-
tions as well, including breaker failure protection, overload protection, and start inhibit
for motors.
Addresses which have an appended "A" can only be changed with DIGSI, under "Dis-
play Additional Settings".
Setting Options
OFF
ON
Alarm Only
40 .. 260 V
40 .. 150 V
0.00 .. 100.00 sec; ∞
40 .. 260 V
40 .. 150 V
0.00 .. 100.00 sec; ∞
2 .. 150 V
2 .. 150 V
0.90 .. 0.99
0.90 .. 0.99
OFF
ON
Alarm Only
10 .. 210 V
10 .. 120 V
0.00 .. 100.00 sec; ∞
10 .. 210 V
10 .. 120 V
0.00 .. 100.00 sec; ∞
2.6 Voltage Protection 27, 59
Default Setting
OFF
59 Overvoltage Protection
110 V
59-1 Pickup
110 V
59-1 Pickup
0.50 sec
59-1 Time Delay
120 V
59-2 Pickup
120 V
59-2 Pickup
0.50 sec
59-2 Time Delay
30 V
59-1 Pickup V2
50 V
59-2 Pickup V2
0.95
59-1 Dropout Ratio
0.95
59-2 Dropout Ratio
OFF
27 Undervoltage Protection
75 V
27-1 Pickup
75 V
27-1 Pickup
1.50 sec
27-1 Time Delay
70 V
27-2 Pickup
70 V
27-2 Pickup
0.50 sec
27-2 Time Delay
Comments
144