3 Mounting and Commissioning

3.3.14 Measuring the Operating Time of the Circuit Breaker (only 7SJ64)

Only for Synchro-
nism Check
437
Temperature in
Temperature in
°C
30
86
40
104
50
122
60
140
70
158
80
176
90
194
100
212
110
230
120
248
130
266
140
284
150
302
160
320
170
338
180
356
190
374
200
392
210
410
220
428
230
446
240
464
250
482
Temperature thresholds that are configured in the protection device can be checked
by slowly approaching the resistance value.
If device 7SJ64 is equipped with the function for synchronism and voltage check and
it is applied, it is necessary – under asynchronous system conditions – that the oper-
ating time of the circuit breaker is measured and set correctly when closing. If the syn-
chronism check function is not used or only for closing under synchronous system
conditions, this subsection is irrelevant.
For measuring the operating time a setup as shown in Figure 3-40 is recommended.
The timer is set to a range of 1 s and a graduation of 1 ms.
The circuit breaker is connected manually. At the same time the timer is started. After
closing the poles of the circuit breaker, the voltage V
stopped. The time displayed by the timer is the real circuit breaker closing time.
If the timer is not stopped due to an unfavourable closing moment, the attempt will be
repeated.
It is particularly favourable to calculate the mean value from several (3 to 5) successful
switching attempts.
In address 6X20 set this time to T-CB close (under Power System Data of the syn-
chronism check). Select the next lower settable value.
Ni 100 DIN 43760 Ni 120 DIN 34760 Pt 100 IEC 60751
°F
117.055771
123.011173
129.105
135.340259
141.720613
148.250369
154.934473
161.7785
168.788637
175.971673
183.334982
190.88651
198.63475
206.58873
214.757989
223.152552
231.782912
240.66
249.79516
259.200121
268.886968
278.868111
289.15625
140.466925
111.672925
147.613407
115.5408
154.926
119.397125
162.408311
123.2419
170.064735
127.075125
177.900442
130.8968
185.921368
134.706925
194.1342
138.5055
202.546364
142.292525
211.166007
146.068
220.001979
149.831925
229.063812
153.5843
238.3617
157.325125
247.906476
161.0544
257.709587
164.772125
267.783063
168.4783
278.139495
172.172925
288.792
175.856
299.754192
179.527525
311.040145
183.1875
322.664362
186.835925
334.641733
190.4728
346.9875
194.098125
appears and the timer is
Line
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015