Undervoltage Protection 27

Application
Function
137
The undervoltage protection function detects voltage collapses on transmission lines
and electrical machines and prevents the persistance of inadmissible operating states
and a possible loss of stability.
With three-phase connection, undervoltage protection uses the positive sequence fun-
damental component or, optionally, also the actual phase-to-phase voltages. The
latter case applies the smallest of the phase-to-phase voltages.
If only one voltage transformer is connected, the function is provided with the phase-
to-ground or phase-phase fundamental component voltage in accordance with the
type of connection.
Undervoltage protection consists of two definite time elements (27-1 PICKUP and
27-2 PICKUP). Therefore, tripping can be time-graded depending on how severe
voltage collapses are. Voltage thresholds and time delays can be set individually for
both elements. The voltage limit values are configured as phase-to-phase quantities.
Thus, either the positive sequence system value V1 · √3 or, optionally, the smallest of
the phase-to-phase voltages is evaluated.
The dropout ratio for the two undervoltage elements (= V
set.
/V
dropout value
pickup value
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
) can be