Setting Notes - Siemens siprotec SJ62 User Manual

Multi-functional protective relay with local control
Table of Contents

Advertisement

2 Functions

2.22.3 Setting Notes

Trip Signal Dura-
tion
313
either by pressing the LED reset key or by activating an appropriately allocated binary
input („>Reset LED"). A precondition, of course, is that the circuit-breaker close coil
– as usual – remains blocked as long as the trip signal is present, and that the trip coil
current is interrupted by the auxiliary contact of the circuit breaker.
Figure 2-112
Terminating the Trip Signal
The minimum trip command duration TMin TRIP CMD was described already in
Section 2.1.3. This setting applies to all protective functions that initiate tripping.
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015