Device Options - Satec EM132 Installation And Operation Manual

Em13 series smart multifunction meter
Hide thumbs Also See for EM132:
Table of Contents

Advertisement

Configuring
‎ C hapter 5

Device Options

Using the Front Display
Options
TestMode
OFF
Using PAS
Table 10: User-configurable Device Options
Display
Label
TestMode
PowMode
EngyRoll
Phs.Engy
StrtVolt
Resolution
EM13x Series SMART MULTIFUNCTION METER
the EM13X Series
The Device Options setup allows changing user-configurable device
options or putting the meter into energy test mode.
Select Options from the main menu. See
Options
in Chapter 3 for information on configuring parameters via the
front display.
Select General Setup from the Meter Setup menu, and then click on
the Device Options tab.
Table 10 lists available device options.
Parameter
Energy Test
Three options:
Mode
OFF = disabled
Wh pulses
varh pulses
Power
Reactive = using reactive power
Calculation
S=f(P, Q),
Mode
NonActive = using non-active
power Q=f(S, P)
Energy Roll
10000 = 10000 kWh
Value
100000 = 100000 kWh
1000000 = 1000000 kWh
10000000 = 10000000kWh
100000000 = 100000000 kWh
1000000000 = 1000000000 kWh
Phase Energy
Disabled
Calculation
Enabled
Starting
1.5-5.0%
Voltage
Device
Low
Resolution
High
Options
Default
Disabled
S=f(P, Q)
10000000
Disabled
1.5%
Low
General Meter Setup
Viewing and Changing Setup
Description
Setting this option puts the
meter into the energy test
mode (see
Energy Pulse
LED
in Chapter 3)
The method used for
calculating reactive and
apparent powers (see
Power Calculation Modes
below)
The value at which energy
counters roll over to zero
Enables phase energy
calculations
The device starting voltage
in percent of FS (120V or
400V)
The voltage, current and
power resolution on the
front display (see
Measurement Units
Chapter 3) and in
communications (see
communication guides)
in
83

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Em133Em133-se

Table of Contents