‎ C hapter 5
Configuring the EM13X Series
Factory Preset Data Log Files
110
Double click on the Data Log#16partition with the left mouse button.
Select the TOU Daily Profile file type.
Select the number of season tariffs in your TOU schedule. Add one
additional parameter if you selected to record the Summary (TOU
total) registers as well.
Select the maximum number of records you want to be recorded in the
file assuming that a new record will be added once a day.
Click OK and send your setup to the meter or save to the meter
database.
Conventional Data Log #1
Data log #1 is factory preset for 15-min periodic recording of the
standard energy and demand quantities. You can freely change the list
of recorded parameters and the file update rate.
The default list of parameters is shown in the following table.
No.
1
kWh import
2
kWh export
3
kW import sliding demand
4
V1 demand
5
V2 demand
6
V3 demand
Periodic recording data is triggered by Setpoint #1 that is linked to the
meter clock. To change the periodic rate at which data is recorded,
change the time interval for the MINUTE INTERVAL trigger in Setpoint
#1 (see
Configuring Alarm/Control
Billing/TOU Profile Data Log #16
Data log #16 is pre-configured for daily billing energy and maximum
demand recording for the last 90 days. It is automatically updated
once a day.
See
Billing Profile Log File
Parameter
Setpoints).
in Appendix E for the file record structure.