Configuring Recorders; Configuring Meter Memory - Satec EM132 Installation And Operation Manual

Em13 series smart multifunction meter
Hide thumbs Also See for EM132:
Table of Contents

Advertisement

‎ C hapter 5
Configuring the EM13X Series

5.5 Configuring Recorders

Configuring Meter Memory

106
The EM13X Series has a 125-KByte onboard non-volatile memory for
data and event recording. The memory is fully configurable and can be
freely partitioned between log files.
The meter provides memory for a total of 3 log files:
Event log
Two data logs
The two data log files are pre-configured at the factory for recording a
15-minute energy and demand profile and for the daily billing energy
data profile. If you wish to change the factory settings, follow the
guidelines in the next section.
To view the present memory settings, select Memory/Log from the
Meter Setup menu, and then click on the Log Memory tab.
Figure ‎ 5 -19: Log Setup Dialog Box – Log Memory Tab
The following table describes file options.
Option
Range
Type
Wrap-
around
Non-wrap
Size
Sections/Channels
0-8
Num. of Records
0-65535
Record size
Parameters
0-9
Description
Wrap-around: recording continues over the oldest
records.
Non-wrap: recording is stopped until the file is
cleared.
The size of memory allocated to the file.
The numbers of sections in a multi-section profile
data log file
Allocates the file memory for predefined number of
records
The size of the file record for a single channel or a
single section. It is set automatically depending on
the file and on the number of parameters in the
data records
The number of parameters in a single data log
record
EM13x Series SMART MULTIFUNCTION METER