Upgrading Device Firmware - Satec EM132 Installation And Operation Manual

Em13 series smart multifunction meter
Hide thumbs Also See for EM132:
Table of Contents

Advertisement

‎ C hapter 6
Device Control and Upgrading
Figure ‎ 6 -6: Device Control Dialog Box – Remote Relay Control Tab
To send a remote command to a relay:

6.6 Upgrading Device Firmware

To download a new firmware file to your device:
120
Select a desired command in the Relay Command box for a relay:
OPERATE – to operate a relay
RELEASE – to remove your remote command, or to release a latched
relay
Click Send.
Your meter has upgradeable firmware. If you need to upgrade your
device, download a new firmware file to the meter through PAS.
Firmware can be downloaded via the MODBUS RTU or MODBUS/TCP
protocol through any communication port.
Ensure that the communication port you are connected through to the
meter operates in Modbus mode.
If you are connected to the meter through a serial interface, it is
recommended to set the port baud rate to 115,200 bps. See
Up Serial Communication Ports
and baud rate in your meter.
Ensure that the On-line button on the PAS toolbar is checked, and
then select Flash Downloader from the Monitor menu and confirm
downloading.
Point to the firmware upgrade file for your meter, click Open, and then
confirm upgrading the meter.
on how to remotely change the protocol