Configuring The Daily Tariff Schedule - Satec EM132 Installation And Operation Manual

Em13 series smart multifunction meter
Hide thumbs Also See for EM132:
Table of Contents

Advertisement

‎ C hapter 5
Configuring the EM13X Series

Configuring the Daily Tariff Schedule

To configure your daily profiles:
104
To configure your daily tariff schedule, select Energy/TOU from the
Meter Setup menu, and then click on the TOU Daily Profiles tab.
Figure ‎ 5 -17: Energy/TOU Setup Dialog Box – TOU Daily Profiles Tab
The daily profile setup allows you to specify the daily tariff change
points with a 15-minute resolution for 4 seasons using 4 different daily
schedules for each season.
Select the desired season and day type.
Select the start time for each tariff change point and the corresponding
active tariff number.
Repeat the setup for all active profiles.
The first tariff change point is fixed at 00:00 hours, and the last tariff
change you specified will be in use until 00:00 hours on the next day.
NOTE
The billing daily profile log file is automatically configured for the
number of active tariffs you defined in the meter TOU daily profiles.