Table 23: Measurement Specifications Parameters
Parameter
Voltage, V
Voltage, V
(EM133-SE model)
Line current, A
Line current -
direct
Active power, kW
Reactive power,
kvar
Apparent power,
kVA
Power factor
Frequency
Total Harmonic
Distortion, THD
V(I), %V f (%I f )
Total Demand
Distortion, TDD, %
Active energy
Import & Export
Reactive energy
Import & Export
Apparent energy
1
@ 80% to 120% of voltage FS, 1% to 200% of current FS at (In = 5 and 1 A), 2% to 200% of
current FS 50 A and frequency 50/60 Hz
150
Measurement Specifications
Full Scale @
InputRange
Reading
120VxPT @ 120V
0.2
400VxPT @ 690V
0.2
V
= 120V,
0.2
L
V
= 230V
0.2
L
CT
0.2
50 A
0.2
0.36PTCT @ 120V
0.3
1.2PTCT @ 690V
34.5 @(230V,50A)
0.36PTCT@ 120V
0.3
1.2PTCT @ 690V
34.5 @(230V,50A)
0.36PTCT @ 120V
0.3
1.2PTCT @ 690V
34.5 @(230V,50A)
1.000
50 Hz
0.02
60 Hz
0.02
25 Hz
0.04
400 Hz
0.04
999.9
1.5
100
In = 5 and 1 A
Class C as per EN50470-3, Class
0.5S under conditions as per
IEC/AZ 62053-22:2003 at 50/60 Hz
& ANSI C12.20 Ac. Class 0.5
In = 5 and 1 A
Class 0.5S under conditions as per
IEC 62053-22:2003, |PF|  0.9 and
at 50/60 Hz
In = 5 and 1 A
Class 0.5S under conditions as per
IEC 62053-22:2003 at 50/60 Hz
PT - external potential transformer ratio
CT - primary current rating of the external current transformer
FSV - voltage full scale
FSI - current full scale
V f - fundamental voltage
I f - fundamental current
Accuracy
%
%
Conditions
FS
0.02
10% to 120%
0.02
10% to 115%
0.02
10% to 120%
0.02
10% to 115%
0.02
For In = 5A
1% to 200% FS
For In = 1A
2% to 200% FS
0.02
2% to 200% FS
1
0.02
|PF|  0.5
1
|PF|  0.9
0.03
1
0.02
|PF|  0.5
|PF|  0.5,
0.2
I  2% FSI
V
> 25V
L-N
THD  1%,
0.2
V  10% FSV and
V
> 25V,
L-N
I  10% FSI
TDD  1%,
1.5
I  10% FSI,
V
> 25V
L-N
EM13x Series SMART MULTIFUNCTION METER
Range
0 to 1,150,000 V
Starting voltage
1.5-5.0% FS (selectable)
80 to 1,150,000 V
Starting voltage 80VAC
(w/1phase)
Starting current 0.1% FS
Starting current 0.1% FS
-10,000,000 kW to
+10,000,000 kW
-10,000,000 kvar to
+10,000,000 kvar
0 to 10,000,000 kVA
-0.999 to +1.000
15 Hz to 70 Hz
15 Hz to 70 Hz
15 Hz to 70 Hz
320 Hz to 480 Hz
0 to 999.9
0 to 100
0 to 999,999,999 kWh
0 to 999,999,999 kvarh
0 to 999,999,999 kVAh