Electrical Installation; Connecting The Wires - Satec EM132 Installation And Operation Manual

Em13 series smart multifunction meter
Hide thumbs Also See for EM132:
Table of Contents

Advertisement

Installation
‎ C hapter 2

2.4 Electrical Installation

Connecting the wires

Table 2: Wiring Configurations
Terminals
Aux. Power
Supply Inputs
L/+, N/-
Voltages Inputs
V1, V2, V3, Vn
Current Inputs
I1, I2, I3, N
Current Inputs
I1, I2, I3, N
COM1, I/O
connections
EM13x Series SMART MULTIFUNCTION METER
The equipment installation shall conform to the following
instructions:
a) a switch or circuit-breaker shall be included in the building
installation as close as possible to the equipment supply
voltage;
b) It shall be in close proximity to the equipment and within
easy reach of the OPERATOR;
c) It shall be marked as the disconnecting device for the
equipment.
d) Before installing, ensure that all incoming power sources are
shut OFF. Failure to observe this practice can result in serious
or even fatal injury and damage to equipment.
e) The current sensors may not be installed in a panel where
they exceed 75% of the wiring space of any cross-sectional
area within the panel.
All conductors must be stranded copper. All conductors and insulation
systems and crimped devices must be appropriate for the application.
SATEC requires using crimped ferrules on stranded wire.
Table 3 below summarizes the different conductors' sizes to be used in
the EM133 external connections.
Conductor size
EM133 model
Minimum
AWG (mm²)
N/A in EM133-
22 (0.5)
SE models
N/A in EM133-
22 (0.5)
SE-100A
EM133/SE-
22 (0.5)
1A, 5A, HACS
EM133/SE-
6 (16)
100A
All Models
22 (0.5)
Torque
Maximum
[Nm]
AWG (mm²)
12 (4.0)
0.5-0.7
12 (4.0)
0.5-0.7
10 (6.0)
1.8-2
4 (25)
2-2.7
12 (4.0)
0.5-0.7
Electrical Installation
Notes
Use 600V insulated conductors
Required crimped ferrule:
Panduit (22AWG) F75-10-M
Panduit (12AWG) F81-15-M
Use 600V insulated conductors
Required crimped ferrule:
Panduit (22AWG) F75-10-M
Panduit (12AWG) F81-15-M
Use 600V insulated conductors
Required crimped ferrule:
Panduit (22AWG) F75-10-M
Panduit (10AWG) F82-15-M
Use 600V insulated conductors
Required crimped ferrule:
Panduit (6AWG) F84-15-M
Panduit (4AWG) F85-15-M
Use 600V insulated conductors
Required crimped ferrule:
Panduit (22AWG) F75-10-M
Panduit (12AWG) F81-15-M
25