Appendix G Data Scales - Satec EM132 Installation And Operation Manual

Em13 series smart multifunction meter
Hide thumbs Also See for EM132:
Table of Contents

Advertisement

‎ A ppendix
Data Scales
G
Appendix G
Table 29: Data Scales Values
Maximum voltage
(V max)
Maximum current
(I max)
Maximum Power
Maximum frequency
168
Data Scales
The maximum values for volts, amps and power in the EM13X Series
setup and in communications are limited by the voltage and current
scale settings.
The following table shows the meter data scales.
Scale
All configurations
All configurations
4
Wiring 4LN3, 3LN3, 3BLN3
Wiring 4LL3, 3LL3, 3BLL3,
3OP2, 3OP3, 3DIR2
25, 50 or 60 Hz
400Hz
1
The default voltage scale is 144V. The recommended voltage scale is
120V+20% = 144V for using with external PT's, and 690V+20% =
828V for a direct connection to power line.
2
CT Ratio = CT primary current/CT secondary current
3
The default current scale is 2  CT secondary (2.0A with 1A secondary
and 10.0A with 5A secondary).
4
Maximum power is rounded to whole kilowatts. With PT=1.0, it is
limited to 9,999,000 W.
Conditions
Voltage scale  PT Ratio, V
Current scale  CT Ratio, A
V max  I max  3, W
V max  I max  2, W
100 Hz
500 Hz
EM13x Series SMART MULTIFUNCTION METER
Range
1
2, 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Em133Em133-se

Table of Contents