Configuring Billing/Tou; Configuring Billing/Tariff Registers - Satec EM132 Installation And Operation Manual

Em13 series smart multifunction meter
Hide thumbs Also See for EM132:
Table of Contents

Advertisement

‎ C hapter 5
Configuring the EM13X Series

5.4 Configuring Billing/TOU

To configure the billing registers and the tariff system in your meter:

Configuring Billing/Tariff Registers

102
Billing Energy Registers
The EM13X Series has 4 fully programmable billing energy registers
that can be linked to any internal energy source or to an external pulse
source that delivers pulses through the meter digital inputs.
Any
energy
register
accumulation or be individually linked to the TOU system providing
both total and multi-tariff energy billing.
Tariff Rates
The meter tariff structure supports 8 different tariff rates using an
arbitrary tariff schedule. A total of 4 types of days and 4 seasons are
supported with up to eight tariff changes per day.
Maximum Demand Registers
Any of billing energy registers can be individually linked to the
maximum demand register providing the same demand tariff structure
as you selected for energy registers.
Recording Billing Data and Load Profiling
The EM13X Series can provide automatic recording of the daily energy
and maximum demand profile to a data log file. Maximum demand
profiling can be individually configured for every register.
See
Factory Preset Data Log Files
File
in Appendix E for more information on the file layout and contents.
Link the billing registers to the respective energy sources.
Configure the options for the registers to whether the only totalization or
both total and tariff registers would be used, and whether daily profiling
should be enabled for the energy usage and maximum demand
registers.
Configure the daily tariff schedule using the TOU daily profiles for all
types of days and seasons.
Configure the season tariff schedule using the TOU calendar.
To configure the billing/TOU registers in your meter:
Select Energy/TOU from the Meter Setup menu.
can
provide
either
in Chapter 5 and
EM13x Series SMART MULTIFUNCTION METER
Configuring Billing/TOU