Display Operations; Navigation Buttons - Satec EM132 Installation And Operation Manual

Em13 series smart multifunction meter
Hide thumbs Also See for EM132:
Table of Contents

Advertisement

Using
‎ C hapter 3
Front Display

3.1 Display Operations

Navigation Buttons

EM13x Series SMART MULTIFUNCTION METER
The EM13X Series has a high-contrast graphical LCD display with
backlight for local data read outs, meter setup and servicing.
The display operates in two modes:
Multi-page data display mode with Auto-Scroll feature allows you to
scroll through display screens and pages to view various billing,
instrumentation and status data.
Programming mode allows you to enter menu-driven device setups
for inspecting and changing factory set meter parameters, or
resetting maximum demands, counters and device diagnostics
messages. The display is normally updated once per second except
of the clock display where the update rate changes to twice per
second.
The EM13X Series is provided with two navigation buttons,
SELECT/ENTERbutton and
You can perform three types of actions with each button:
Short press, or "press and release"
Long press, or "press and hold for 1 to 2 seconds"
Extended press, or "press and hold for 5 seconds or longer "
The function of each button changes depending on what operating
mode the display is in.
The SCROLL button operates once it is briefly pressed. It has two
functions:
In data display mode, it scrolls through the display pages.
In programming mode, it scrolls through the menu items and allows
changing a selected digit when entering numbers.
The SELECT/ENTER button normally operates once it's released. The
button function changes depending on the time the button is pressed:
In data display mode, when pressed briefly and released, it scrolls
through the display views; a long press for more than 5 seconds
switches to programming mode.
In programming mode, when pressed briefly and released, it moves
from one menu item to another; a long press for one second selects
a highlighted menu item allowing to enter a submenu or to store a
changed item.
In data display mode, when the SCROLL and SELECT/ENTER buttons
are briefly pressed together and then released, the current display
returns to the start page; in some pages, an extended press for more
than 5 seconds is used as a "shortcut" for immediate entering a
specific programming menu.
SCROLL button.
Display Operations