A feature of the Smart DC Controller is its 24-hour, 365 day clock. Make sure
it is set to the appropriate time zone. An accurate time and date allows the
diagnostic log to date stamp operational data which indicates when Alerts,
Faults and Errors occur. The log helps in troubleshooting and can be viewed
using the S.T.A.R.T. software application via a laptop connected to the USB or
RS-232 port. For more information, refer to Smart Touch Analyze and Retrieve
Tool (S.T.A.R.T.) on page 71.
To set or adjust the time or date, take the following steps:
1. At a gate status display, press the MENU button twice. This accesses
the User Menu and the CLOSE TIMER display appears.
2. Press NEXT or PREV until the SET CLOCK display appears.
3. Press SELECT.
4. CL blinks.
5. Press NEXT or PREV to change the number to 1.
6. Press SELECT to accept the display.
7. The date and time display appears. Use the SELECT and NEXT
buttons in the same manner as before to adjust the date and time.
NOTE: A date or time field must be blinking before it
can be changed.
8. To accept what appears on the date and time display, press SELECT.
9. To exit the User Menu, press the MENU button. A gate status appears
in the display indicating you have returned to Run Mode.
NOTE: A lithium coin battery supports the clock so the date and time is retained even when
the main power is turned off. Replace the battery about every five years with a DL 2025, DL
2032 or CR 2025 or CR 2032 battery. Refer to Clock Battery Replacement.
r
o
esettIng
Resetting the open and close limits is easily accomplished by accessing the
Installer Menu.
Press MENU twice at
Status Display
the Run Mode static display.
GATE CLOSED
User Menu
CT 0 (OFF)
To access the Installer Menu,
press and hold RESET &
OPEN, and then release them.
30
MX3650-01 Rev. D
t
d
Ime and
ate
C
pen and
lose
Press Select.
Installer Menu
The "LL" characters blink.
LL 0 (OFF)
Learn Limits
LL 1 (ON)
Press Next.
StrongArmPark DC Programming & Operations
l
ImIts
LEARN OPEN
DEGS: +XXX.X
Press Select. The Learn OPEN blinks in the display
indicating that the operator is ready to relearn the
closed limit.
HYSECURITY
GATE CLOSED
OPEN
CLOSE
STOP
MENU
PREV
NEXT
SELECT
CT 0 (OFF)
CLOSE TIMER
CLOSE
MENU
OPEN
STOP
PREV
NEXT
SELECT
CL 1
SET CLOCK
CLOSE
MENU
OPEN
STOP
PREV
NEXT
SELECT
01/05/13
00:00
^^
OPEN
CLOSE
STOP
MENU
NEXT
SELECT
PREV
© 2017
www.hysecurity.com
RESET
RESET
RESET
RESET