The StrongArmPark DC has separate Installation Instructions that explain how to connect to AC power. For
reference purposes, the same information is provided below.
Size the primary wires. Consider the voltage and length of the wire run from the main power panel. Make sure
you have set the voltage selector switch to the proper voltage.
DANGER
Turn OFF AC power at the source (circuit breaker panel) before accessing the wires in the
StrongArmPark DC. Follow facility Lock Out/Tag Out procedures. Make sure all power switches are in
the OFF position. Follow all electrical code standards and regulations.
CAUTION
Wiring of gate operators must conform to NFPA and NEC standards and comply with all local codes. When the
installation is compliant and complete, turn on AC power at the source and power module.
DO NOT connect the
WARNING
115VAC service outlet to
208 or 230VAC power supply wires! To use
the 115VAC service outlet on a 208 or
230VAC installation, the electrician needs
to run an extra neutral wire to the operator
from the power source and wire the service
outlet per code.
14
MX3650-01 Rev. D
oWer
Place power switches
in OFF position.
Service outlet
StrongArmPark DC Programming & Operations
When connecting
CAUTION
to 208/230VAC
power, the voltage selector
switch on the AC power board
must be moved to the 230V
position or damage to the
operator will occur and void the Warranty. The label on the high voltage cover
must be changed to state 230V.
High voltage cover
Voltage selector
switch is factory
set to 115V.