HySecurity StrongArmPark DC Programming And Operations Manual page 72

With hysecurity smart dc controller mx3650-01 revision d
Hide thumbs Also See for StrongArmPark DC:
Table of Contents

Advertisement

Alert/Fault/Error
Display
I²C BUS ERROR
DETECTOR FAULT
ON TOO LONG
STIFF GATE
STUCK GATE
NO TARGET
BAD COIN BATTERY
62
MX3650-01 Rev. D
Table 8: Troubleshooting Codes
Type
Buzzer
ALERT 10
2 chirps/s
An Hy5x vehicle detector:
every 15s
Communications error alert.
Hy5x has been removed or there's a lack
of integrity of the socket connection.
The display indicates which detector the
alert applies to: Exit Loop (ELD), Inside
Arming Loop (IALD), Outside Arming Loop
(OALD), Center Loop (CLD).
ALERT 11
2 chirps/s
An Hy5x vehicle detector: Malfunction
every 15s
alert Caused by a fault within the Hy5x.
The display indicates which detector the
alert applies to: Exit Loop (ELD), Inside
Arming Loop (IALD), Outside Arming Loop
(OALD), Center Loop (CLD).
ALERT 12
2 chirps/s
The Smart DC Controller has an active
every 15s
loop input (Hy5x or box detector output)
for more than 5 minutes. The SDC "sees"
an active loop for more than 5 minutes.
The "active" loop can be actual or false.
The display indicates which detector the
alert applies to: Exit Loop (ELD), Inside
Arming Loop (IALD), Outside Arming Loop
(OALD), Center Loop (CLD).
ALERT 13
2 chirps/s
The SDC detects a gate that, over time, is
every 15s
requiring more power to move it. Usually
caused by degrading gate hardware
or debris in a slide gate track, this alert
appears in the history log. It does not
affect opening or closing the gate.
ALERT 14
2 chirps/s
The SDC detects that it cannot move the
every 15s
gate at all possibly caused by broken gate
hardware or ice/snow buildup.
ALERT 15
2 chirps/s
The target magnet on the StrongArmPark
every 15s
DC or on the chain (SlideSmart DC) is
missing or has not been detected.
ALERT 17
3 chirps
The small battery on the SDC is loose or
at initial
needs replacing.
power up
StrongArmPark DC Programming & Operations
Possible Cause
Suggested Corrective Action
Remove and re-install the Hy5x and
press RESET. Replace the Hy5x, if
necessary.
If communication is not re-
established within 30 seconds,
the controller will reset and the
message changes to
ERROR 3.
Remove and re-install the Hy5x and
press RESET. Replace the Hy5x, if
necessary.
1. Check traffic patterns at the site
and make sure that a vehicle is
not parked on the loop.
2. Determine if the loop is stable.
An unstable loop can hold the
detector in a triggered state.
3. The loop and lead in wires
should be checked for problems
and replaced, if necessary.
4. Check sensitivity setting on the
detector.
1. Check and correct gate hardware
as required.
2. Check motor brushes for
excessive wear.
1. Manually move the gate. Verify
that it moves easily and is
unobstructed throughout gate
travel.
2. Check and correct gate
hardware, as required.
1. Make sure target is properly
fastened. Did you move it or
unscrew it? Is the target magnet
or wires to it, broken?
2. Red LED light flashes in
the upper left corner of the
controller when it senses the
target. Did the red LED light
flash while opening or closing
the gate? If not, target is missing.
1. Check for current software,
install update, if necessary.
2. Verify that the battery is properly
seated.
3. Replace coin battery.
4. Restore power.
5. Press RESET button.
© 2017
www.hysecurity.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents