HySecurity StrongArmPark DC Programming And Operations Manual page 37

With hysecurity smart dc controller mx3650-01 revision d
Hide thumbs Also See for StrongArmPark DC:
Table of Contents

Advertisement

Installer Menu
SR 0 (FULL OPEN)
0 = Reverses full open
IES Sensor Logic
1 = ½ second reversal (.5)
PC 0 NO CONTACT
0 = Normal Open PE output
1 = Normal Closed (monitored)
Photo Eye Output
GC 0 NO CONTACT
0 = Normally Open Edge
1 = Normally Closed
Gate Edge Output
DT 0 FREE EXIT
0 = Disable Free Exit
1 = Disable Close Timer
Disable Function
OR 1 REVERSE
0 = Pause closing only
Outer Arm Loop
1 = Enable reversing to open
2 = Ignore and continue closing
IR 1 REVERSE
0 = Pause closing only
Inner Arm Loop
1 = Enable reversing to open
2 = Ignore and continue closing
DL 1 STANDARD
1 = Standard
Detector Logic
2 = Quick Close
www.hysecurity.com
© 2017
Table 4: Installer Menu
Setting Options
Display & Menu Options
Menu Tasks & Explanations
The default setting is a ½-second duration
reversal if the dynamic reversing sensor is
triggered. The optional setting of 0 will cause
the gate to reopen fully if triggered while
closing.
The default setting is photo eyes with Normally
Open outputs. Setting 1 requires a Normally
Closed (NC) output which requires both a
photo EYE OPEN and a photo EYE CLOSE
are connected. If set for NC, the connection
is supervised and any open or short circuit
fault will generate a FAULT 2 which requires a
STOP button reset to re-enable any functions
triggered.
The default setting is edge sensor with
Normally Open (NO) output. The optional
setting of 1 requires an (NC) output.
Configures the BLOCK EXIT input to disable
either the Free Exit Detector function or,
alternately, the Timer To Close function. The
default setting disables the free exit detector.
NOTE: The free exit is disabled when the
gate is at its closed limit. If the closed limit is
not tripped, the free exit continues to work
normally.
The default is for full reversal when the loop is
triggered. A setting of 0 causes the barrier arm
to only pause when triggered. Closure begins
as soon as the loop is clear again. A setting
of 2 is provided for the most secure facilities
where it is essential that the loop trigger
is completely ignored and the barrier arm
continues closing without pause or reversal.
The default is for full reversal when the loop is
triggered. A setting of 0 causes the barrier arm
to only pause when triggered. Closure begins
as soon as the loop is clear again. A setting
of 2 is provided for the most secure facilities
where it is essential that the loop trigger
is completely ignored and the barrier arm
continues closing without pause or reversal.
Configures for faster closure. This selection
determines whether the close timer begins
to count after vehicles have departed the
detector loops or whether the close timer will
count down while the loops are occupied.
The default setting 1 causes the Close Timer to
start when the Center Loop is clear. A setting
of 2 causes the Close Timer to start when the
open limit switch trips.
SDC Wire
Connections
N/A
EYE OPEN
EYE CLOSE
4 wires total:
COM/+24
COM/ PHOTO EYE
CLOSE
COM
EDGE
COM
BLOCK EXIT
OUT OBS LOOP
(OUTER ARMING)
COM or connection
to Hy5x detector
IN OBS LOOP
(INNER ARMING)
COM or connection
to Hy5x detector
Center Loop
COM or connection
to Hy5x detector
MX3650-01 Rev. D
27