HySecurity StrongArmPark DC Programming And Operations Manual page 15

With hysecurity smart dc controller mx3650-01 revision d
Hide thumbs Also See for StrongArmPark DC:
Table of Contents

Advertisement

Install the gate operator on the secure (non-public) side of the gate. Note that swing gates cannot open into
public areas.
Install external entrapment protection sensors so pedestrians are protected from entrapment in both directions
of gate travel and all hazard areas are fully protected. On hydraulic gates, set the pressure relief valve at the
lowest allowable setting that will reliably operate the gate. The pressure relief valve controls the applied force of
the operator and the sensitivity of the inherent entrapment sensor (IES). Note that no IES exists in the StrongArm
operator or Crash products.
Never disable the Warn Before Operate buzzer. This buzzer provides an alert that the gate is about to move.
Mount access control devices beyond reach of the gate. The control devices that operate the gate must:
• Be located in a clear line of sight to the gate. Locate controls (Open, Close, Stop/Reset) where a user will
have a clear view of the gate.
• Be mounted beyond 6 feet (183 cm) of the gate, to prevent users from touching or accessing the gate while
operating the controls. People attempting to access the controls by reaching through or around the gate can
be seriously injured or killed by the moving gate.
• Incorporate a security feature to prevent unauthorized use.
• Connect radio and other remote access (non-resetting controls) to the RADIO OPTIONS terminal.
Open and close the gate to confirm that it was properly installed and to ensure reduced risk of entrapment.
Verify the clearance between the gate and adjacent structures per UL 325 Safety Standards. Have a qualified
technician test the gate monthly.
When you complete the installation, demonstrate the safety features and operation of the gate operator to the
end user:
• Clearly explain and demonstrate the consequences of removing or defeating any of the safety features.
• Remove the operator cover(s), and then turn the power on and off.
• Manually release the gate. (Manually release only when the gate is NOT moving.)
• Use the Emergency Stop Button. (If an emergency stop button is not available, show the user where the Stop
button is located on the gate operator.)
NOTE: Gate operator instructions must be given to the owner per UL 325 Safety Standards.
Take photographs of the completed installation site and save it in your business files.
www.hysecurity.com
© 2017
SAVE THESE INSTRUCTIONS
Safety
MX3650-01 Rev. D
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents