Parameter
Name
No.
Application Function
2
Selections 2
Speed/Position Control Option (T-REF Input Allocation)
n.
X
Torque Control Option (V-REF Input Allocation)
n.
X
Pn002
Encoder Usage
n.
X
External Encoder Usage
n.X
5.1 SERVOPACKs with Analog Voltage/Pulse Train References
Setting
Setting
Range
Unit
0000 to
–
4213
0
Do not use T-REF.
1
Use T-REF as an external torque limit input.
2
Use T-REF as a torque feedback input.
Use T-REF as an external torque limit input when
3
/P-CL or /N-CL is ON.
0
Do not use V-REF.
1
Use V-REF as an external speed limit input.
0
Use the encoder according to encoder specifications.
1
Use the encoder as an incremental encoder.
2
Use the encoder as a single-turn absolute encoder.
0
Do not use an external encoder.
The external encoder moves in the forward direction for CCW
1
motor rotation.
2
Reserved setting (Do not use.)
The external encoder moves in the reverse direction for CCW
3
motor rotation.
4
Reserved setting (Do not use.)
5.1.2 List of Parameters
Continued from previous page.
Default
Applicable
When
Setting
Motors
Enabled
After
0000
–
restart
Continued on next page.
Classi-
Refer-
fication
ence
*1
Setup
Applicable
Motors
All
Applicable
Motors
All
Applicable
Motors
All
Rotary
Applicable
Motors
Rotary
5
5-5