YASKAWA SGD7S series Product Manual page 167

Servopack with ft/ex specification for tracking application
Hide thumbs Also See for SGD7S series:
Table of Contents

Advertisement

Warning Number:
Possible Cause
Warning Name
A.95F:
An undefined
Command Warning
command was
6 (Undefined Com-
sent.
mand)
The MECHA-
TROLINK Com-
munications Cable
is not wired cor-
rectly.
A.960:
A MECHA-
MECHATROLINK
TROLINK data
Communications
reception error
Warning
occurred due to
noise.
A failure occurred
in the SERVO-
PACK.
For a 200-V SER-
VOPACK, the AC
power supply volt-
age dropped
below 140 V.
The power supply
voltage dropped
during operation.
A.971:
A momentary
Undervoltage
power interrup-
tion occurred.
The SERVOPACK
fuse is blown out.
A failure occurred
in the SERVO-
PACK.
A command that
A.97A:
cannot be exe-
cuted in the cur-
Command Warning
rent phase was
7 (Phase Error)
sent.
The set com-
mand data was
A.97b:
clamped to the
Data Clamp Out of
minimum or maxi-
Range
mum value of the
setting range.
4.2 SERVOPACKs with MECHATROLINK-III Communications References
Confirmation
Check the command
that caused the warn-
ing.
Check the wiring con-
ditions.
Confirm the installation
conditions.
Measure the power
supply voltage.
Measure the power
supply voltage.
Measure the power
supply voltage.
4.2.6 Troubleshooting Warnings
Continued from previous page.
Correction
Do not send undefined
commands.
Correct the MECHA-
TROLINK communications
cable wiring.
Implement the following
countermeasures against
noise.
• Check the MECHA-
TROLINK Communica-
tions Cable and FG wiring
and implement counter-
measures to prevent noise
from entering.
• Attach a ferrite core to the
MECHATROLINK Com-
munications Cable.
The SERVOPACK may be
faulty. Replace the SERVO-
PACK.
Set the power supply volt-
age within the specified
range.
Increase the power supply
capacity.
If you have changed the
setting of Pn509 (Momen-
tary Power Interruption Hold
Time), decrease the setting.
Replace the SERVOPACK
and connect a reactor.
The SERVOPACK may be
faulty. Replace the SERVO-
PACK.
Send the command after
the command conditions
are satisfied.
Set the command data
within the setting ranges.
Continued on next page.
Reference
*
*
*
*
4
4-99