Figure 15: Power Supply Via Two Power Supply Units - WAGO -I/O-SYSTEM 750 User Manual

Wago-i/o-ipc-c10e 758-875/000-112 canopen master codesys 2.3
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

44
Power Supply
To connect the supply cable for the I/O-IPC electronic supply and for feeding in
the field supply for the connected I/O modules, sensors and actuators through the
power supply module, proceed as follows:
1.
Disconnect from the power supply those parts of the system on which you
have mounted the I/O-IPC.
2.
Connect the electronic supply cable to the I/O-IPC by connecting power
supply cable socket to the I/O-IPC X4 plug (10). Provide this supply with a
1.6A fuse.
3.
Then, secure the socket using the screws supplied for this purpose.
4.
To feed in the field supply, connect the 750-602 Supply Module (5)
according to the illustration, with 24V to "+" and 0V to "-". Provide this
supply with a 10A fuse.
10
1,6 A
+
24 V
Electronic power supply

Figure 15: Power supply via two power supply units

V_IN
GND
-
0 V
10 A
Field power supply
WAGO-I/O-SYSTEM 750
I/O-IPC-C10E, CANopen Master
5
+
-
24 V
0 V