Table 43: I/O-IPC Operational Messages
Position LED
35
36
37
38
39
40
WAGO I/O-SYSTEM 750
I/O-IPC-C10E, CANopen Master
Color/Status
U2
Green, red, off,
flashing
U1
Green, red, off,
flashing
IDE/PWR
Green
Red
IO
Green-red
flashing
Green
Red, flashing
ERR
Red
STA
Yellow
OFF
Cause
Explanation/Remedy
LED that can be
freely programmed by
-
the user (using
MiscLib.lib).
LED that can be
freely programmed by
-
the user (using
MiscLib.lib).
24V supply voltage is
available on the I/O-
IPC.
24V supply voltage is
available on the I/O-
IPC and it is being
accessed on the
internal flash memory
or the CF card.
The I/O-IPC is in the
startup phase.
No malfunction on the
I/O-IPC.
Display of error
Evaluate the error
message through
code (see Section
blink code.
15.2).
The I/O-IPC has
detected a
communication
Check the CoDeSys
problem on at least
configuration.
one CANopen slave
(STA LED also lights
up).
There may be a
defective CAN cable. Check the CAN
cables for damage and
replace them if
required.
The I/O-IPC is
sending CANopen
telegrams.
The I/O-IPC is ready
to receive or is
-
receiving CANopen
telegrams.