7.3
Power Supply with 750-602 Supply Module
With this type of power supply, the length of the power supply cable shall not
exceed 3 meters from the voltage source to the I/O-IPC X4 connection. If a longer
cable is necessary, power shall only be supplied as described in Section 7.4.
Requirements for connecting the power supply:
•
You have connected two supply lines each to two voltage sources of
+24VDC and 0VDC in a de-energized state.
•
You have connected the accompanying socket for the X4 connection to the
supply cable (see table below).
•
You have connected the 750-602 Supply Module to the I/O-IPC.
Ensure the correct conductor cross-section!
Use conductor cross-sections from 0.08 mm² to 2.5 mm² (28 - 14 AWG) only for
the X4 connection and for the CAGE CLAMP® connections of the power supply
module.
The following table provides the pin assignments for the electronic supply
connection.
Table 11: Connection for Electronic Supply: Terminal Layout
X4 connector
3
2
WAGO I/O-SYSTEM 750
I/O-IPC-C10E, CANopen Master
Note
NOTICE
Pin
1
1
2
3
Description
V_IN (+)
GND (-)
Shield (optional)
Power Supply
43