6.4
Securing the I/O-IPC to a Mounting Rail
For installing the I/O-IPC on a mounting rail, there are four clamp levers on the
underside that secure the I/O-IPC to the mounting rail.
If you use mounting rails with a height of 7.5 mm, then use flat riveting or sunken
screws to fasten the mounting rail. Otherwise, the I/O-IPC and the connected I/O
modules cannot be mounted correctly on the mounting rail.
Proceed as described below for mounting:
1.
Disconnect from the power supply those parts of the system on which you
wish to mount the I/O-IPC.
2.
To set the I/O-IPC on the mounting rail (25), press the four release levers
(20) together at the same time until they stop. Press the I/O-IPC onto the
mounting rail and then let the release levers go.
3.
Check that the I/O-IPC is securely placed on the mounting rail. All four
wedges (22) must be locked behind the edge of the mounting rail.
4.
If a side is not locked, press the corresponding release levers together, press
the unlocked side onto the mounting rail and then let go of the release levers
again.
Figure 11: Securing of the I/O-IPC to a mounting rail
WAGO I/O-SYSTEM 750
I/O-IPC-C10E, CANopen Master
Note
20
20
22
Installing and Removing the I/O-IPC
25
22
37