Description of Device Functions
96
11.7.2
Function group Operation
OUTPUTS CURRENT OUTPUT 1 EAA CONFIGURATION 400
VALUE SIMULATION
CURRENT
(4042)
Functional description
!
Note!
The function is not visible unless the function SIMULATION CURRENT (4041) is
active (= ON).
Use this function to define a freely selectable value (e.g. 12 mA) to be output at the
current output. This value is used to test downstream devices and the measuring
device itself.
User input:
Floating-point number: 0.00...25.00 mA
Factory setting
0.00 mA
"
Caution!
The setting is not saved if the power supply fails.
Proline Prosonic Flow 93T Portable
Endress+Hauser