Installation
16
3.6.1

Mounting the sensor holder

• Sensor: Prosonic Flow (DN 15 to 65 / ½ to 2½")
• Sensor holder: Model 1 or 2
Model 1
1.
Set the sensor distance determined (e.g. A19) on the sensor holder.
– Release the screws of the sensor holders.
– Position the sensor holders with the aid of the mounting rail.
– Tighten the screws of the sensor holders again.
A B C D E F G H I K
1 3 5 7 9 11 13 15 17 19 21 23 25 27
A B C D E F
1 3 5 7 9
Fig. 8:
Setting the sensor distance with the mounting rail (value from POSITION SENSOR function)
A
Sensor distance for measurement via one traverse
B
Sensor distance for measurement via two traverses
2.
Guide the sensor holder over the pipe.
Fig. 9:
Setting the sensor holder on the pipe
A
A B C D E F G H I K
Proline Prosonic Flow 93T Portable
B
1 3 5 7 9 11 13 15 17 19 21 23 25 27
Endress+Hauser
A0011548
A0011549