F1.05
Stop mode
0: Dec stop. The inverter reduces output frequency gradually according to set
Dec time upon receival of stop command and stops running after frequency is
reduced to 0.
1: free stop. The inverter stop outputting at once when receiving stop
command and the load stops freely according to mechanical inertia.
2: Dec plus DC braking stop. The inverter reduces output frequency gradually
according to set Dec time upon receival of stop command and start DC braking
when F1.06 stop braking initiative frequency is reached.
F1.06
Stop DC braking initiative frequency
F1.07
Stop DC braking time
F1.08
Stop DC braking voltage
F1.08 is percentage relative to inverter rated input voltage. Have no DC
braking process if stop braking time is 0.0s,as shown in Fig.6-8.
6.3 Auxiliary run function parameter group: F2
F2.00
Analog filtering time constant
The time constant used when the inverter filter sampled value when frequency
is set by exterior analog channel. Can improve the situation by increasing this
filtering time constant if connecting wire is long or disturbance is serious which
cause unstable set frequency.
EDS800 series Service Manual
Output freq.
output volt.
(virtual
value)
run command
Fig.6-8 Dec stop+DC braking
stop braking
initiative freq.
DC braking value
stop braking time
Range:0, 1, 2
Range:0.0-15.00Hz
Range:0.0-20.0S
Range:0-15(%)
Range:0.00-30.00S
58
0
0.00Hz
0.0S
0
0.20S