(1) This function is effective for all Acc/Dec process except for jog run.
(2) To choose second as time unit is recommended.
note
F0.08
Acc time 1
F0.09
Dec time 1
Accelerating time is defined as time for inverter accelerating from 0Hz to high
limit frequency,see t
decelerating from high limit frequency to 0Hz, see t
high limit frequency
(1) In EDS800 series inverter 7 kinds of Acc/Dec time are defined in total, here we
only define Acc/Dec time 1,Acc/Dec time 2~7 are defined in F2.18~F2.29,
please refer to Section 6.3.
note
(2) Can choose time unit minute or second for Acc/Dec time 1~7 by F0.07, factory
default is second.
F0.10
high limit frequency
F0.11
low limit frequency
Low limit freq. run
F0.12
mode
The inverter will decrease output frequency gradually in set decelerating time
when actual set frequency is lower than low limit frequency, after reaching low limit
frequency,the inverter will run at low limit frequency if F0.18 is set to 0;The
inverter will reduce output frequency sequentially to zero frequency run if F0.12 is
set to 1.
F0.13
Torque boost mode
0: manual boost. Torque boost voltage is determined completely by parameter
EDS800 series Service Manual
Range:0.1-6000.0
Range:0.1-6000.0
in Fig.6-3,Dec time is defined as time for inverter
1
Output freq.
t
1
Fig.6-3 Acc/Dec time definition
Range:low limit-400.00Hz
Range:0.00-high limit
Range:0:run at low limit freq. 1:stop
Range:0:manual 1:automatic
54
in Fig.6-3.
2
time
t
2
running
20.0
20.0
50.00Hz
0.00Hz
0
0