7.3 Failure reset

(1) Before reset you must find out reason of failure downright and eliminate it, otherwise
may cause permanent damage to the inverter.
!
(2) If can't reset or failure takes place again after resetting, should look for reason and
continuous resetting will damage the inverter.
(3) Reset should take place 5 minutes after overload, overheat protection action.
To resume normal running when failure takes place in the inverter, you can
choose following any kind of operation:
⑴Set any one terminal of X1~X5 to external RESET input (F5.00~F5.04=11),
open it after connected to COM.
⑵When failure code is displayed,press
⑶Cut off power supply.
EDS800 series Service Manual
STOP
RESET
107
key after restoration is confirmed.