it will keep the former frequency running the electric on .
11: terminal PWM pulse set frequency.
Relation between frequency and input information is determined by function code
F7.00~F7.17 when frequency input channel is 4, 5, 6, 7,please see Section 6.8.
note
F0.01
Freq. digital setting
F0.01 parameter is original set frequency of the inverter when frequency setting
channel is defined as number setting (F0.00=1, 3).
F0.02
Run command channel selection
0: keypad run frequency command channel. Start and stop the inverter
by
,
,
RUN
STOP
1: terminal run command channel(keypad STOP command ineffective).
Start and stop the inverter by exterior control terminal FWD, REV, X1~X5 etc..
2: terminal run command channel(keypad STOP command effective). Start
and stop the inverter by exterior control terminal FWD, REV, X1~X5 etc..
3: serial port run command channel(keypad STOP command ineffective).
Start and stop the inverter by RS485 interface.
4: serial port run command channel(keypad STOP command effective).
Start and stop the inverter by RS485 interface.
The inverter can change run command channel by modifying F0.02 during waiting and
!
running,please confirm that modification is allowed during running on the spot.
F0.03
Run direction setting
This function is only effective for keypad and serial port run command channel
ineffective for terminal run command channel.
The 1st bit:
0: inverter forward run
1: inverter reverse run
The 2nd bit:
0: reverse run allowed
1: reverse run banned. The inverter will stop output when there is reverse run
command.
The 3rd bit: REV/JOG key selection
0: as REV key
1: as JOG key
EDS800 series Service Manual
key on the keypad.
REV
JOG
Range:low limit ~high limit
Range:0~4
Range:0, 1
52
50.00Hz
0
100