F0.06
S curve risetime
accelerating
F0.07
decelerating time
unit
Acce time 1
F0.08
F0.09
Dece time 1
F0.10
Upper limit freq.
F0.11
Lower limit freq.
F0.12
Lower limit freq.
run mode
F0.13
Torque boost
mode
F0.14
Torque boost
F0.15
V/F curve setting
F0.16
reserved
Function
name
code
F1.00
Start-up run mode
F1.01
start-up freq.
F1.02
start-up freq. duration
F1.03
Zero freq. DC braking volt.
F1.04
Zero freq. DC braking time
F1.05
Stop mode
DC brake initiative freq.
F1.06
when stop running
DC brake time when stop
F1.07
running
DC brake voltage when stop
F1.08
running
EDS800 series Service Manual
10.0(%)-70.0(%) (Acce/Dece time)
F0.05+F0.06≤90(%)
0: second
1: minute
0.1-6000.0
0.1-6000.0
Lower limit freq.-400.00Hz
0.00-Upper limit freq.
0: run at lower limit freq.
1: stop running
0: manual boost
1: automatic boost
0.0-20.0(%)
0: constant torque curve
1: degressive torque curve 1(the 2.0nd power)
2: degressive torque curve 2(the 1.7th power)
3: degressive torque curve 3(the 1.2th power)
4: End-user sets VF curve himself(determined by
F2.37~F2.44)
F2.37
VF Freq. value 0
F2.38
VF voltage value 0
F2.39
VF Freq. value 1
F2.40
VF voltage value 1
F2.41
VF Freq. value 2
F2.42
VF voltage value 2
F2.43
VF Freq. value 3
F2.44
VF voltage value 3
Remark: VF frequency and voltage can't be 0
or maximum
F1 –start-up, stop, brake function parameter group
0: start at start-up freq.
1: first brake, then start at start-up freq.
2: reserved
0.0-10.00Hz
0.0-20.0S
0-15(%)
0.0-20.0S
0: Dec stop
1: free stop
2: Dec+DC brake stop
0.0-15.00Hz
0.0-20.0s
0-15(%)
Set range
36
0.1(%) 60.0(%)
1
0
0.1
20.0
0.1
20.0
0.01Hz 50.00Hz
0.01Hz 0.00Hz
1
0
1
0
0.1(%) 4.0(%)
1
0
0.01Hz
0.50Hz
0.01%
2.00%
0.01Hz
20.00Hz
0.01%
38.00%
0.01Hz
25.00Hz
48.00%
0.01%
0.01Hz
40.00Hz
0.01%
80.00%
Factory
Modificat-
unit
default
ion
1
0
0.01Hz 0.00Hz
0.1s
0.0s
1
0
0.1s
0.0s
1
0
0.01Hz 0.00Hz
0.1s
0.0s
1
0
○
×
○
○
×
×
×
○
○
×
×
○
○
○
○
×
○
○
○