Protection function
Fitting parts
Use ambient
altitude
Ambient temperature
Ambient humidity
vibration
Storage temperature
Defending grade
Config-
uration
Cooling mode
Mounting mode
To exert excellent performance of this inverter, please choose correct type and check
note
relevant content according to this chapter before wiring for use.
Must choose correct type, otherwise may cause abnormal running of the motor or
!
damage
EDS800 series Service Manual
Over-current protection, over-voltage protection, lack-voltage
protection, over-heat protection, over-load protection, missing phase
protection (in option)etc.
brake subassembly, remote-control keypad, connecting cable for
remote-control keypad etc.
indoor,not bare to sunlight,no dust, no corrosive gas, no flammable
gas, no oil fog, no vapor, no water drop or salt etc.
Lower than 1000m
-10ºC~+40ºC(under ambient temperature 40ºC ~50ºC, please reduce the
volume or strengthen heat sink)
Smaller than 95%RH, no condensation water
Smaller than 5.9m/s²(0.6g)
-40ºC~+70ºC
IP20
By fan with automatic temperature control
Wall hanging
9