SHENZHEN ENCOM ELECTRIC TECHNOLOGIES CO. enc eds800-2s0002n User Manual page 110

Eds800 series
Table of Contents

Advertisement

Inverting
E013
module
protection
external
device
E014
failure
current
E015
detecting circuit
failure
RS485
E016
communication
failure
EDS800 series Service Manual
Transient overcurrent of the
inverter
phase to phase short
circuit or earthing short
circuit of output 3 phase
Air-path blocked or fan
damaged
Ambient temperature is too
high
Connecting wire or insert on
control board
loose
Unwonted
current
caused by missing
output phase etc.
Assistant power supply
damaged and drive
voltage lacking
Unwonted control board
use sudden stop
STOP
key in non-keypad run
mode
Use sudden stop
STOP
key under condition of
stall
Sudden stop terminal for
external failure closed
Connecting wire or
insert on control board
loose
Assistant power supply
damaged
Hall component
damaged
Unwonted amplifying
circuit
Baud rate set improperly
Serial port
communication error
Failure warning
parameter set improperly
Upper device doesn't
work
105
Refer to countermeasure for
overcurrent
wiring again
To clear air-path or replace the
fan
Lower ambient temperature
Check and connect the wire again
wave
Check wiring
Look for service from
manufacturer or agent
Look for service from
manufacturer or agent
Look up operation mode
Set running parameter correctly
Open external failure terminal after
external failure is settled
Check and connect the wire again
Look for service from
manufacturer or agent
Look for service from
manufacturer or agent
Look for service from
manufacturer or agent
set Baud rate properly
STOP
press
RESET
for service
Modify F2.16, F2.17
Check if upper device work and
wiring is correct
key to reset,look