Error Code Description
101B DC16 External UPS: battery not low (informational
message)
101B DC56 Informational message about the IBF.
101B DC66 Informational message about the IBF.
101B DC76 Informational message about the IBF.
101B DD16 External UPS: bypass ended (informational
message)
101B DF16 Problem with external UPS: UPS failure
101B E106 Critical logic over temperature
101B E206 Ambient room temperature too high
101B F4x6 Hardware configuration does not support
N-mode power
101B F806 BPC B: loss of ac power or phase missing
101B F906 BPC B: loss of ac power or phase missing
101B FA06 BPC B: loss of ac power or phase missing
101B FDB6 BPC B: open room EPO switch has been
detected
101B FE06 UEPO switch on BPC B is in the bypass position Go to "MAP 1522: UEPO Switch On The BPC Is
101B FE16 UEPO switch on BPC B is in the bypass position Go to "MAP 1522: UEPO Switch On The BPC Is
101B FE56 BPR 1B communications fault
426
Eserver pSeries 690 Service Guide
Action/
Possible Failing FRU
Informational message. If a problem is
suspected:
1. Verify the cabling between the UPS and the
BPCs.
2. Refer to the manufacturer's documentation
for the UPS.
3. Call service support.
Informational message.
Informational message.
Informational message.
Informational message. If a problem is
suspected:
1. Verify the cabling between the UPS and the
BPCs.
2. Refer to the manufacturer's documentation
for the UPS.
3. Call service support.
1. Verify the cabling between the UPS and the
BPCs.
2. Refer to the manufacturer's documentation
for the UPS.
3. Call service support.
Go to "MAP 1528: There Is A Processor
(Critical/Warning) Overtemperature Fault" on
page 207.
1. The ambient room temperature has reached
a warning level or a critical level. Ask the
customer to correct the room temperature
problem.
2. Call service support.
Call service support.
Go to "MAP 152a: Loss of ac Power or Phase
Missing" on page 210.
Go to "MAP 152a: Loss of ac Power or Phase
Missing" on page 210.
Go to "MAP 152a: Loss of ac Power or Phase
Missing" on page 210.
Go to "MAP 1524: An Open Room EPO Switch
Has Been Detected From One Side" on
page 198.
In The Bypass Position" on page 197.
In The Bypass Position" on page 197.
Go to "MAP 1523: There Is a Bulk Power
Regulator (BPR) Communications Fault" on
page 198.