IBM pSeries 690 Service Manual page 439

Hide thumbs Also See for pSeries 690:
Table of Contents

Advertisement

Error Code Description
101A DC66 Informational message about the IBF.
101A DC76 Informational message about the IBF.
101A DD16 External UPS: bypass ended (informational
message)
101A DF16 Problem with external UPS: UPS failure
101A E106 Critical logic over temperature
101A E206 Ambient room temperature too high
101A F4x6 Hardware configuration does not support
N-mode power
101A F806 BPC A: loss of ac power or phase missing
101A F906 BPC A: loss of ac power or phase missing
101A F806 BPC A: loss of ac power or phase missing
101A F906 BPC A: loss of ac power or phase missing
101A FA06 Problem with EPO switch detected by BPC-A
101A FDB6 BPC A: open room EPO switch has been
detected
101A FE06 UEPO switch on BPC A is in the bypass position Go to "MAP 1522: UEPO Switch On The BPC Is
101A FE16 UEPO switch on BPC A is in the bypass position Go to "MAP 1522: UEPO Switch On The BPC Is
101A FE56 BPR 1A communications fault
101A FE66 BPR 2A communications fault
Action/
Possible Failing FRU
Informational message.
Informational message.
Informational message. If a problem is
suspected:
1. Verify the cabling between the UPS and the
BPCs.
2. Refer to the manufacturer's documentation
for the UPS.
3. Call service support.
1. Verify the cabling between the UPS and the
BPCs.
2. Refer to the manufacturer's documentation
for the UPS.
3. Call service support.
Go to "MAP 1528: There Is A Processor
(Critical/Warning) Overtemperature Fault" on
page 207.
1. The ambient room temperature has reached
a warning level (30 C) or a critical level (36
C). Ask the customer to correct the room
temperature problem.
2. Call service support.
Call service support.
Go to "MAP 152a: Loss of ac Power or Phase
Missing" on page 210.
Go to "MAP 152a: Loss of ac Power or Phase
Missing" on page 210.
Go to "MAP 152a: Loss of ac Power or Phase
Missing" on page 210.
Go to "MAP 152a: Loss of ac Power or Phase
Missing" on page 210.
Go to "MAP 152a: Loss of ac Power or Phase
Missing" on page 210.
Go to "MAP 1524: An Open Room EPO Switch
Has Been Detected From One Side" on
page 198.
In The Bypass Position" on page 197.
In The Bypass Position" on page 197.
Go to "MAP 1523: There Is a Bulk Power
Regulator (BPR) Communications Fault" on
page 198.
Go to "MAP 1523: There Is a Bulk Power
Regulator (BPR) Communications Fault" on
page 198.
Chapter 5. Error Code to FRU Index
419