Ann-S/Pg Serial/Parallel Interface Installation - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Product Description
The following table shows the ANN-80 connections to the MS-9200UDLS.
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must be added to the system via FACP programming. Refer to the programming section titled
"ANN-BUS Options" on page 120 in this manual for detailed programming information. Select
the LCD option for programming.
Trouble Response
If the ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the ANN-80 will indicate
a trouble condition by NOT turning on its AC Power indicator. The LCD will also display Key Bus
Trouble and the piezo will sound approximately once every 10 seconds. Note that the FACP will
provide no indication of an ANN-80 trouble.
To clear the ANN-80 trouble condition, enable the ANN-BUS and program the address correspond-
ing to the address set on the ANN-80 at the FACP.

ANN-S/PG Serial/Parallel Interface Installation

The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel
printer to the FACP for a real-time log of system events, detector status reports and event history.
The module is provided with a plastic enclosure for surface mounting. Proceed with the installation
as described in the following:
1.
Ensure that all power (AC and DC) has been removed from the FACP.
2.
Connect the ANN-S/PG to the FACP as illustrated in Figure 1.7
JP7
1
2
3
3.
Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address)
to the module
30
MS-9200UDLS
Terminal GND (-) on TB1
Terminal PWR (+)TB1
Terminal Data (A) on TB9
Terminal Data (B) on TB9
ANN-BUS and power wiring are
supervised and power-limited
24 VDC
nonresettable
+
-
TB1
TB2
+
-
+ 24V -
+ 24V -
REMOTE PWR
RST
NON-RST
SUPPLY SYNC
POWER
POWER
Figure 1.7 ANN-S/PG Connection to FACP
ANN-80 (TB1)
Terminal 1 (-)
Terminal 2 (+)
Terminal 3 (A)
Terminal 4 (B)
(-)
(+)
A
B
Primary ANN-BUS
ANN
TB10
SLC
SLC
SHIELD
TB9
SLC
SLC
B+ A+ B- A-
A
B
ACS
A B
+ -
MS-9200UDLS
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
Accessories
Parallel
Cable Connectors for
connection to printer
Serial
ANN-S/PG Module